Photo 2.11.5.2
LA-P Installed in the Front Panel Receptacle
2. INSTALLATION
32
2.11 Options,
continued
2.11.5 Rack-mount Options
The APC Rack-mount options include: ACAT-3P; TDR-M; and LA-P (LA-E for 230
VAC models). These options are mounted in a slightly different manner.
CAUTION: BEFORE PROCEEDING, ENSURE THAT THE UTILITY POWER HAS
BEEN DISCONNECTED!
2.11.5.1 ACAT-3P and TDR-M Photo 2.11.5.1
Procedure:
1. Mount these options on the rear of the unit and secure with one (1) SEMS
screw. The screw is inserted from the front panel of the APC.
See Photo 2.10.5 for placement.
2. Connect the proper connector into the option. NOTE: If installing a TDR-M
you will first need to remove the 3-pin shorting connector.
Photo 2.11.5.1
ACAT-3P and TDR-M Installed in the APC Rack-mount
2.11.5.2 LA-P (120VAC Models) - Photo 2.11.5.2
Procedure:
The LA-P simply plugs into the front panel of the APC Rack-mount. See Photo
2.11.5.2