The shelf-mount version of the APC (APL) consists of the standard MTA (Modular
Transformer Assembly) which rests on a mounting plate (SM). The mounting plate
and MTA can then be installed into an enclosure such as the PED- M, PWE or
UPE. The shelf-mount option also includes an input AC power extension cable
(APC model only) and an APC - SPI adaptor.
NOTE: BEFORE INSTALLING THE APC, ENSURE THAT ALL OPTIONS HAVE
BEEN INSTALLED AND PROPERLY CONNECTED. REFER TO SECTION 2.11
OPTIONS, FOR INSTALLATION INSTRUCTIONS.
Procedure: Photos 2.6.a, .b, .c
1. Place the modular transformer assembly (MTA) onto the shelf-mount (SM)
by fitting the slot on the top of the MTA over the tab on the SM bracket.
2. Locate the captive screw on the opposite side of the shelf-mount adaptor
(next to the terminal block). Fit this captive screw into the threaded portion
of the MTA and tighten.
3. Place the assembled shelf-mount bracket and modular transformer
assembly into the shelf of the enclosure (PED-M, PWE or UPE). Place one
of the key-slot holes over the threaded screw hole in the enclosure’s shelf.
Install a 8-32 x 1/2” long screw and tighten. NOTE: Only one of the screw
holes is used to mount the SM onto the enclosures shelf. To install
additional APC-SM’s into the enclosure, you will need to drill and tap
another mounting hole.
4. Connect the AC input power extension cable to the AC power cable on the
unit. Connect the plug of the extension cable into the enclosures AC
receptacle.
NOTE: The APL model is connected to the utility power via the terminal block on the
MTA
5. Output connection to the plant is accomplished via the terminal block or by
using SPI the APC - SPI adaptor cable.
6. The APC (APL) is now ready for the utility connection (see section 3.1
START-UP AND TEST).
2.6 Shelf-mount Installations
Photo 2.6.a
Shelf Mount (SM)
2. INSTALLATION
17
Power Extension
Cable
APC Output
Connection Block
SPI Adaptor
Cable
Shelf Mount
Captive Screw