CFR3000 and 3000RMUninterruptible Power SuppliesFrom Alpha Technologies!!!!! Operator’s Manual
1 Introduction41.2 Unpacking and Inspection Checklist (Continued)Complete the following for your recordsSerial # __________________________________Opt
5 1 Introduction1.3 The Alpha CFR 3000 and 3000RM1.3.1 Front PanelTIP: Unless otherwise shown in this manual, the 3000 and 3000RM are identical andope
1 Introduction61.3 The Alpha CFR 3000 and 3000RM (Continued)3000 Rack Mount (RM)ALARM OFFMANUALSTARTOUTPUT LO ADOVERLOAD100%75%50%25%LINE PRESENTLINE
7 1 Introduction1.3 The Alpha CFR 3000 and 3000RM (Continued)1.3.2 Rear PanelFigure 1.1Rear Panels3000RM3000Fan (3000 Only)This fan cools the unit. It
1 Introduction81.3 The Alpha CFR 3000 and 3000RM (Continued)Input Circuit BreakerThis provides protection for the unit. It canbe used as an input powe
9 1 Introduction1.3 The Alpha CFR 3000 and 3000RM (Continued)RS-232 ConnectorThis DB–9 port is the RS–232 connection(Section 2.6).LAN Interface Connec
10Section 2InstallationThis section shows you how to installand connect the Alpha CFR 3000 and3000RM UPS’s:• A pre-installation checklist (Section 2.
11 2 Installation2.1 Pre–Installation Checklist2.1.1 Site PreparationInstall the unit upright in a dry, well-ventilated, dust free environment. There
2 Installation 12The unit should be wired to dedicated circuit equipped with a properly sized circuit breaker.The breaker’s size is the unit’s maximum
13 2 Installation2.2 Installing the Unit2.2.1: CFR 3000TIP: The seismic brackets can be removed if they are not required by the local code oryou are n
!!!!!Operator’s Manual!!!!!CFR 3000 and 3000RMUninterruptible Power SuppliesALARM OFFMANUALSTARTOUTPUT LOADOVER L OAD100%75%50%25%LINE PRESENTLINE FA
2 Installation 142.2 Installing the Unit (Continued)5 If the brackets are not needed, remove the cover and the front panel as described in Sec-tion 5.
15 2 Installation2.3 Connecting the Unit2.3.1: Plug and ConnectorDanger: All wiring must meet the local electrical code. Mark all circuit breakers sup
2 Installation 162.3.2: Terminal BlockDanger: All wiring must meet the local electrical code. Mark all circuit breakers supply-ing power to the unit.
17 2 Installation2.3 Connecting the Unit (Continued)ycneuqerFycneuqerFycneuqerFycneuqerFycneuqerF *egatloV*egatloV*egatloV*egatloV*egatloVzH06zH06zH06
2 Installation 182.4 Connecting the External Battery PackDANGER: There are hazardous voltages inside the battery packs. Use extreme cau-tion. For mor
19 2 Installation2.4 Connecting the External Battery Pack (Continued)Figure 2.6Connecting an External Battery Pack to the 3000245Figure 2.5Connecting
2 Installation 202.5 Connecting the External Alarm PortAn external alarm panel can be connected to the external alarm port (Figure 2.7). The port’scon
21 2 Installation2.6 Connecting the RS–232 PortThe unit can be remotely setup, monitored, and tested by connecting the unit’s DB–9 connectorto a compu
2 Installation 222.7 Connecting the LAN PortThe unit can be remotely monitored and shutdown with the unit’s DB–9 LAN port (Figure 2.9).Two dry contact
23 2 Installation2.8 Transformer Output Load Sharing2.8.1: Transformer OutputThe units have a single phase output. They do NOT have three phase charac
CFR 3000 and 3000RMNOTICE:The CFR 3000 and 3000RM generates, uses and can radiate radio frequencies if not installed andtested in accordance with the
2 Installation 242.8 Transformer Output Load Sharing (Continued)2.8.2.1: Measuring the Output CurrentThis uses a clip-on current probe (Figure 2.12 fo
25 2 Installation2.8 Transformer Output Load Sharing (Continued)2.8.2.2: Displaying the Output CurrentTIP: When using the display panels, you must cal
26Section 3OperationThis section shows you how to operatethe Alpha CFR 3000 and 3000RM UPS’s:• How to turn the unit on and off (Sections 3.1, 3.2).• H
27 3 Operation3.1 Turning On the UnitWARNINGS:1) The unit runs warm to the touch. During the first few weeks of operation, a brand newunit may give of
3 Operation28Cold Start ProcedureThis starts the unit with battery power when line power is unavailable or unqualified. Backupbattery power is provide
29 3 Operation3.2 Turning Off the UnitThe emergency shutdown procedure is on the inside rear cover.Procedure:1 One at time, turn off the loads.2 Switc
3 Operation303.3 Testing the UnitThe self test confirms the unit can switch from line to backup battery power and back withoutinterrupting power to th
31 3 Operation3.4 Troubleshooting With the SIDThe SID’s Output Load LEDs have two functions:• When the unit is operating normally, it serves to show t
3 Operation323.5 Controlling the Unit with the Standard Interface Device (SID)The Standard Interface Device (SID) display panel (Figure 3.4) shows vit
33 3 OperationLow Battery ShutdownThis red LED turns on when the battery voltage is 12% below nominal. The unit automati-cally shuts itself down and n
CFR 3000 and 3000RMSafety ChecklistsDANGER: Sealed lead-acid batteries with high energy and chemical hazards areused. This manual contains important o
3 Operation343.5 Controlling the Unit with the Standard Interface Device (SID) (Continued)Output LoadThese five green LED's show the unit’s loadi
35Section 4CommunicationThis section shows you how to controlthe Alpha CFR 3000 and 3000RM UPS’swith RS–232 commands:• How to set up communications wi
4 Communication364.1 RS–232 Set-UpWire the DB–9 connector as shown in Section 2.6, “Connecting the RS–232 Port.”Windows HyperTerminal Connection For
37 4 Communication4.1 RS–232 Set-Up (Continued)4The Com 1 Properties screen appears(Figure 4.3). Fill out the fields as shown.5Click OK.Figure 4.3COM
4 Communication384.2 Using the Opening MenuThe opening menu (Figure 4.5, also see Figure 4.4) is the top-level menu. It shows the line’sstatus, displa
39 4 Communication4.2 Using the Opening Menu (Continued)Figures 4.6 to 4.9 list the alarms, how they appear on the screen and what they mean.Figure 4.
4 Communication404.2 Using the Opening Menu (Continued)Figure 4.9Environmental and Service AlarmssmralAecivreSdnalatnemnorivnEsmralAecivreSdnalatnemno
41 4 Communication4.3 Menu Tree• To reach any main or sub menu from the opening menu, type its number and press Enter.• Detailed descriptions of each
4 Communication424.4 System, Input, Output & Battery ParametersMain menus #1 to #4 are read only menus which display important operating paramete
43 4 Communication4.4 System, Input, Output & Battery Parameters (Continued)4.4.3 Main Menu #3: Output ParametersThis displays selected output pa
CFR 3000 and 3000RMiiiSafety Checklists (Continued)Live battery wires must not touch the unit’s chassis or any other metal objects. This cancause a fi
4 Communication444.4 System, Input, Output & Battery Parameters (Continued)Output Terminal BlockLNOutput Voltage 1230 VAC ReceptacleOutput Curren
45 4 Communication4.5 User ParametersMain menu #5, user parameters, lets you set up the automatic self test, remotely shut down theunit, change the p
4 Communication464.5 User Parameters (Continued))deunitnoC(sretemaraPresU)deunitnoC(sretemaraPresU)deunitnoC(sretemaraPresU)deunitnoC(sretemaraPresU)
47 4 Communication4.5 User Parameters (Continued))deunitnoC(sretemaraPnwodtuhStuptuOteS)deunitnoC(sretemaraPnwodtuhStuptuOteS)deunitnoC(sretemaraPnwo
4 Communication484.5 User Parameters (Continued)4.5.3 Sub Menu #56: Transmit Unsolicited AlarmsThese menus allow you to prevent or delay the continuo
49 4 Communication4.6 Maintenance ParametersMain menu #7, maintenance parameters, allows you to adjust the unit’s detection and warningparameters to
4 Communication504.7 Installing and Using the External ModemUses of the External ModemWhere a network is not available, you can connect an external m
51 4 CommunicationStep 1: Enable the CFR’s Modem FeatureThe CFR is shipped with the modem feature disabled. To enable it:1 Connect a computer to the C
4 Communication524.7 Installing and Using the External Modem (Continued)Step 2: Connect and Configure the ModemUse a shielded, null-modem serial cabl
53 4 Communication3 The initialization string (Item #527) is a set of commands the CFR sends to themodem to initialize it. For a US Robotics modem, th
CFR 3000 and 3000RMivTable of ContentsThe emergency shutdown procedure is on the inside rear cover1. Introduction ...
4 Communication54Step 3: Initalize the ModemTo initalize the modem start a CFR self test (Section 3.3).The CFR must initialize the modem. If a remote
55 4 Communication4.7 Installing and Using the External Modem (Continued)How the CFR Sends AlarmsTo send an alarm, the CFR sends the dial command to
4 Communication564.7 Installing and Using the External Modem (Continued)Figure 4.22External Modem Setup Menu ItemssuneMputeSmedoMlanretxEsuneMputeSme
57 4 Communication4.7 Installing and Using the External Modem (Continued))deunitnoC(suneMputeSuneMmedoMlanretxE)deunitnoC(suneMputeSuneMmedoMlanretxE
58Section 5MaintenanceThis section describes how to maintainthe Alpha CFR 3000 and 3000RM UPS’s:• How to measure the battery back up time (Sec-tion 5.
59 5 Maintenance5.1 Testing the Battery Backup TimeThis test measures how long the batteries can provide backup power by having them power theloads un
5 Maintenance 605.2 TroubleshootingMost problems involve:• Are the Input, Battery and Output circuit breakers switched on?• Is the input voltage corre
61 5 Maintenance5.2 Troubleshooting (Continued)Figure 5.1Troubleshooting Table (Continued)motpmySmotpmySmotpmySmotpmySmotpmyS esuaCesuaCesuaCesuaCesua
5 Maintenance 625.3 Returning the CFR to Alpha for RepairsBefore returning a unit for repair, obtain a Return Material Authorization (RMA) number from
63 5 Maintenance5.4 Replacing the Internal Batteries (Continued)Tools and Materials Required:• Phillips Screwdriver.•7/16 and 3/8 inch wrenches for th
1Section 1IntroductionThis section introduces you to the AlphaCFR 3000 and 3000RM UPS’s:• The CFR advantage (Section 1.1).• An unpacking and inspectio
5 Maintenance 645.4 Replacing the Internal Batteries (Continued)Step 2: Charger Voltage TestThis tests the unit’s charger so the new batteries will no
65 5 Maintenance5.4 Replacing the Internal Batteries (Continued)Step 3: Battery ReplacementProcedure:1 Disconnect the negative (black) battery leadfro
5 Maintenance 665.4 Replacing the Internal Batteries (Continued)7 Put the battery foam blocks on top of the batteries.8 Attach the positive (red) batt
67 5 Maintenance5.5 Configuring the Input/Output VoltageThe unit is factory configured to your input/output voltage specifications.• Units configured
5 Maintenance 685.5 Configuring the Input/Output Voltage (Continued)3 For the CFR 3000RM, remove the front panel by unscrewing the 6 screws and liftin
69 5 Maintenance5.5 Configuring the Input/Output Voltage (Continued)Figure 5.6High Voltage Board123456789101112 TB1W4S1JP1-JP6W3W5W2W1Figure 5.7High V
5 Maintenance 705.6 Battery Run TimesThe times in these charts are to be used in conjunction with the battery run time you measured inSection 5.1, “Me
71 5 Maintenance5.6 Battery Run Times (Continued)skcaPyrettaBMRA84PBEhtiw)MR0003RFC(sledoMtnuoMkcaRskcaPyrettaBMRA84PBEhtiw)MR0003RFC(sledoMtnuoMkcaRs
5 Maintenance 725.7 SpecificationssnoitacificepSlacinahceMsnoitacificepSlacinahceMsnoitacificepSlacinahceMsnoitacificepSlacinahceMsnoitacificepSlacina
73Index120 VAC OutputConnecting Loads To ...23–253000Battery Charger Test ...
1 Introduction21.1 The CFR Advantage! Advanced Power Protection TechnologyAlpha’s CFR Uninterruptible Power Supply (UPS) provides continuous and condi
74IndexFront Panel ...6RS–232 Connector... 9, 21Site S
75IndexIIIDExternal Connector ... 9Location of... 5,
76IndexPPack, External Battery, Installation...18–19Panel, Operate Unit With SID...32–34Panel, Front, Removing
77IndexTransformer Output, Overloading ... 23Troubleshooting ...31, 60–61Tower Mounting
Warranty78Alpha Technologies warrants its equipment to be free of manufacturing defects in material and workmanshipfor a period of 24 months from the
To order parts or for technical information, contact Alpha Technologies customer service de-partment directly at::setatSdetinU:setatSdetinU:setatSdet
Alpha sales and service offices located throughout the world© 2003 Alpha Technologies http://www.alpha.comPrinted In Canada 017–108–B0 06 / 0
3 1 Introduction1.2 Unpacking and Inspection ChecklistTIP: If items are missing or damaged, contact Alpha and the shipping company atonce. Most shippe