240VAC Service (XM Series 2 915-240 Power Supply; XM Series 2 922-
48 for UPE-4 and UPE-8): Enclosures used with the XM
Series 2 915-240 or 922-48 are equipped with a 240VAC
duplex receptacle to provide power to the power supply
and peripheral equipment. The receptacle, NEMA 6-15R,
is protected by a single, 2-pole, common trip 15
Amp circuit breaker located inside the service entrance.
Wiring is typically 14AWG per NEC code, a grounding
clamp, located on the enclosure, facilitates dedicated
grounding.
120VAC 20A Service (XM Series 2 915-120 Power Supply): Enclosures used
with the XM Series 2 915-120 are equipped with a
120VAC duplex receptacle to provide power to the
power supply and peripheral equipment. The receptacle,
NEMA 5-20R, is protected by a single, 2-pole, common
trip 20 Amp circuit breaker located inside the service
entrance. Wiring is typically 12AWG per NEC code, a
grounding clamp, located on the enclosure, facilitates
dedicated grounding.
120VAC 15A Service (XM Series 2 615): Enclosures used with the XM Series
2 615 are equipped with a 120VAC duplex receptacle
to provide power to the power supply and peripheral
equipment. The receptacle, NEMA 5-15R, is protected
by a single-pole, 15 Amp High Magnetic circuit breaker
located inside the service entrance. Wiring is typically
14AWG per NEC code, a grounding clamp, located on
the enclosure, facilitates dedicated grounding.
NOTE: Alpha recommends wiring with 12AWG, in case the enclosure
is to be upgraded to use 90V power supplies in the future.
2.2 Utility Power Connection, continued
2. Installation
12 031-106-C1-001 Rev. A