Alpha Technologies®PWE/PME SeriesPole and Ground-mount EnclosuresPWE/PME Series Technical ManualEffective: April 2009
031-161-B0-006, Rev. F101.0 Introduction, continued1.1 PWE/PME Series EnclosuresPWE-D36PWE-4 PWE-8PWE-9PWE-6 PMEPWE-3Fig. 1-2, PWE/PME Series Enclosu
11031-161-B0-006, Rev. F1.0 Introduction, continued1.2 PWE Enclosure DiagramKnockoutsfor Status MonitoringOptional SPI LocationsStandard SPI Location
031-161-B0-006, Rev. F121.0 Introduction, continued1.3 Optional FeaturesFeature DescriptionAC Indicator (ACI) The ACI verifies voltage output with a g
13031-161-B0-006, Rev. F1.0 Introduction, continued1.4 The Battery Integration TrayThe optional Battery Integration Tray (BIT) eliminates the need fo
031-161-B0-006, Rev. F141.0 Introduction, continued1.5 PWE Battery Tray Latch Operation (optional)As an added safety precaution, the PWE series featu
15031-161-B0-006, Rev. FTable 1-1, PME/PWE Enclosure Specifi cations1.0 Introduction, continued1.6 PWE Lid Removal1.7 PWE/PME Enclosure Specifi cation
031-161-B0-006, Rev. F162.0 InstallationCAUTION!• Never transport the unit with installed batteries. Doing so can cause injury or damage to the enclo
17031-161-B0-006, Rev. F2.0 Installation, continued2.1 Pole-mounting, continued2.1.1 Wooden Pole, continued5. Secure the brackets to the pole using t
031-161-B0-006, Rev. F182.0 Installation, continued2.1 Pole-mounting, continued2.1.2 Concrete or Steel PoleTools and Materials Required (customer sup
19031-161-B0-006, Rev. F2.0 Installation, continued2.1 Pole-mounting, continued2.1.2 Concrete or Steel Poles, continuedFig. 2-2, PWE/PME Series Steel
PowerAlpha Technologies®
031-161-B0-006, Rev. F202.0 Installation, continued2.1 Pole-mounting, continued2.1.3 Enclosure Grounding: Pole-mountAlpha recommends using the ground
21031-161-B0-006, Rev. F2.0 Installation, continued2.2 Ground-mount Installation: PWE-4, PWE-8, PWE-9, PWE-D36Never transport the unit with installed
031-161-B0-006, Rev. F22Fig. 2-4, Ground-mount Positioning and Safety2.0 Installation, continued2.2 Ground-mount Installation: PWE-4, PWE-6, PWE-8, PW
23031-161-B0-006, Rev. F2.0 Installation, continued2.2 Ground-mount Installation: PWE-4, PWE-8, PWE-9, PWE-D36, continued2.2.2 Enclosure Grounding:
031-161-B0-006, Rev. F242.0 Installation, continued2.2 Ground-mount Installation PWE-4, PWE-8, PWE-9, PWE-D36, continued2.2.3 Ground-mount Installat
25031-161-B0-006, Rev. F2.0 Installation, continued2.2 Ground-mounting PWE-4, PWE-8, PWE-9, PWE-D36, continued2.2.3 PWE-9 and PWE-D36 Ground-mount I
031-161-B0-006, Rev. F262.0 Installation, continued2.2 Ground-mount Installation, PWE-4, PWE-8, PWE-9, PWE-D36, continued2.2.4 PWE-4 and PWE-8 Groun
27031-161-B0-006, Rev. F2.0 Installation, continued2.2 Ground-mount Installation, PWE-4, PWE-8, PWE-9, PWE-D36, continued2.2.4 PWE-4 and PWE-8 Groun
031-161-B0-006, Rev. F28ONLY qualifi ed personal should connect the utility power. Power must be connected in compliance with local electrical codes, a
29031-161-B0-006, Rev. F240Vac Service (XM2-915 240 Power Supply; XM Series 2 922-48 for PWE-4 and PWE-8)Enclosures used with the XM Series 2, model 9
member of The GroupTM PWE/PME Technical Manual031-161-B0-006, Rev. FEffective Date: April 2009Copyright© 2009Alpha Technologies, Inc.To con
031-161-B0-006, Rev. F302.0 Installation, continued2.3 Connecting Utility Power, continuedFig. 2-12, Typical Service Entrance WiringL1 (Black)L1 (Bla
31031-161-B0-006, Rev. F2.0 Installation, continued2.3 Connecting Utility Power, continuedISE 240V 15AISE 120V 20 AISE 120V 15AGroundLine 1Line 2Grou
031-161-B0-006, Rev. F322.0 Installation, continued2.3 Connecting the Utility Power, continuedGroundLine 1Line 2GroundLineNeutralONOFFONOFFGroundLine
33031-161-B0-006, Rev. F2.0 Installation, continued2.3 Connecting the Utility Power, continuedAlpha offers a Meter Convenience Assembly (MCA) as a co
031-161-B0-006, Rev. F342.0 Installation, continued2.3 Connecting Utility Power, continuedGround ClampLine 2Neutral BusNeutralLine 2#8 AWG (Min.) Cop
35031-161-B0-006, Rev. F2.0 Installation, continued2.4 Connecting the Coaxial Cable2.4.1 Coaxial Cable Surge Protector Installation InstructionsAlph
031-161-B0-006, Rev. F36Disconnect all power sources from the SPI (Service Power Inserter) before removing its cover. Verify that the SPI is disconnec
37031-161-B0-006, Rev. F2.0 Installation, continued2.5 Battery Installation2.5.1 Battery Date Code Usage and Identifi cationEvery battery contains a D
031-161-B0-006, Rev. F382.0 Installation, continued2.5 Battery Installation, continued2.5.2 Battery Installation Procedure Procedure:1. Place the b
39031-161-B0-006, Rev. F2.0 Installation, continued2.5 Battery Installation, continued2.5.3 Connecting the Battery Integration Tray (PWE 3/6 Only)1.
031-161-B0-006, Rev. F4List of Tables and FiguresSafety Notes ...
031-161-B0-006, Rev. F40• Various types of batteries with different mounting styles and hardware may be shipped with the system. ALWAYS refer to the
41031-161-B0-006, Rev. FFig. 2-26, Flag Battery Terminal Connections2.0 Installation, continued2.5 Battery Installation, continued2.5.4 Battery Term
031-161-B0-006, Rev. F422.0 Installation, continued2.5 Battery Installation, continued2.5.5 Battery Wiring Diagrams Fig. 2-27, PWE-3 (without BIT) a
43031-161-B0-006, Rev. F2.0 Installation, continued2.5 Battery Installation, continued2.5.5 Battery Wiring Diagrams, continued Fig. 2-29, PWE-6 Bat
031-161-B0-006, Rev. F441A2A3A1B2B3BR E D (+)B L A C K (-)R E D (+)B L A C K (-)2.0 Installation, continued2.5 Battery Installation, continued2.5.5
45031-161-B0-006, Rev. F Fig. 2-31, PWE-8 Battery Wiring Diagram2.0 Installation, continued2.5 Battery Installation, continued2.5.5 Battery Wiring
031-161-B0-006, Rev. F462.0 Installation, continued2.5 Battery Installation, continued2.5.5 Battery Wiring Diagrams, continued Fig. 2-32, PWE-9 Bat
47031-161-B0-006, Rev. F4. After verifying that the batteries, battery connections, and battery cables are connected properly, plug the battery cable
031-161-B0-006, Rev. F482.0 Installation, continued2.7 Cooling Fan Installation• This procedure requires a service power supply (for example, an APP
49031-161-B0-006, Rev. FDrill only in the fi ve locations indicated below. Center punches marked with a “ ” (6 places) below are reserved for the st
5031-161-B0-006, Rev. FList of Tables and FiguresFig. 1-1, PWE-6 Enclosure ...
031-161-B0-006, Rev. F502.0 Installation, continued2.9 Status Monitoring Transponder Bracket Installation InstructionsTools and Materials Required:•
51031-161-B0-006, Rev. F3.0 Pole-mount Enclosure MaintenancePreventive Maintenance should be performed every three to six months. Inspect the Pole-mo
PowerAlpha Technologies®Due to continuing product improvements, Alpha reserves the right to change specifi cations without notice. Copyright © 2009 Alp
031-161-B0-006, Rev. F6Safety NotesReview the drawings and illustrations contained in this manual before proceeding. If there are any questions regard
7031-161-B0-006, Rev. FBattery Maintenance GuidelinesThe battery maintenance instructions listed below are for reference only. Battery manufacturer’s
031-161-B0-006, Rev. F8Battery Safety NotesLead-acid batteries contain dangerous voltages, currents and corrosive material. Battery installation, main