Alpha-technologies Cordex Controller Ver.2.0 Manual do Utilizador Página 114

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 126
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 113
Refer to the back of this manual for Factory Service and Technical Support contact information
Alpha Technologies Ltd. 034-136-C0 Rev B WC
Printed in Canada. © 2010 Alpha Technologies Ltd. ALPHA and CORDEX are trademarks of Alpha Technologies Ltd. All Rights Reserved. Page 112 of 122
Submenu Item Programmable Range Default Setting
12Vdc 24Vdc 48Vdc 125Vdc 220Vdc
LVD 1 0-9999999999 10.5V 21.00V 42.00V 101.50V 178.50V
LVC 1 0-9999999999 12.5V 25.00V 50.00V 120.83V 212.50V
Alarm Priority Major/Minor/Message Major
Relay Mapping 1-16 or N/A (mapping disabled) 1
Control Check = enable LVD control Checked
Alarm cutoff Check = allow alarm to be cutoff Not checked
LVD 2 0-9999999999 10.5V 21.00V 42.00V 101.50V 178.50V
LVC 2 0-9999999999 12.5V 25.00V 50.00V 120.83V 212.50V
Alarm Priority Major/Minor/Message Major
Relay Mapping 1-16 or N/A (mapping disabled) 2
Control Check = enable LVD control Checked
Alarm cutoff Check = allow alarm to be cutoff Not checked
LVD 3 0-9999999999 10.5V 21.00V 42.00V 101.50V 178.50V
LVC 3 0-9999999999 12.5V 25.00V 50.00V 120.83V 212.50V
Alarm Priority Major/Minor/Message Major
Relay Mapping 1-16 or N/A (mapping disabled) 3
Control Check = enable LVD control Checked
Alarm cutoff Check = allow alarm to be cutoff Not checked
LVD 4-10 0-9999999999 10.5V 21.00V 42.00V 101.50V 178.50V
LVC 4-10 0-9999999999 12.5V 25.00V 50.00V 120.83V 212.50V
Alarm Priority Major/Minor/Message Major
Relay Mapping 1-16 or N/A (mapping disabled) N/A
Control Check = enable LVD control Not checked
Alarm cutoff Check = allow alarm to be cutoff Not checked
LVD Inhibit (Status) Active/Inactive Inactive
Alarm Priority Major/Minor/Message Major
Relay Mapping 1-16 or N/A (mapping disabled) N/A
Alarm cutoff Check = allow alarm to be cutoff Not checked
High Volt. Shutdown 0-9999999999 14.25V 29.50V 58.00V 140.17V 246.50V
Alarm Priority Major/Minor/Message Major
Relay Mapping 1-16 or N/A (mapping disabled) N/A
Control Check = enable LVD control Not checked
Alarm cutoff Check = allow alarm to be cutoff Not checked
CEMF In-circuit Voltage 0-9999999999 13.70V 27.40V 54.80V 132.43V 232.90V
Bypass Voltage 0-9999999999 13.55V 27.10V 54.20V 130.98V 230.35V
Alarm Priority Major/Minor/Message Major
Relay Mapping 1-16 or N/A (mapping disabled) N/A
Control Check = enable LVD control Not checked
Alarm cutoff Check = allow alarm to be cutoff Not checked
Table J–Controls menu defaults
Vista de página 113
1 2 ... 109 110 111 112 113 114 115 116 117 118 119 ... 125 126

Comentários a estes Manuais

Sem comentários